illustrative picture
PK 120X55 D HD - parapetní kanál dutý
pk120x55d_vykres.jpg
To download 3D models, please login or create an account and request access.
EAN code8595057650572
Customs code39259020
წონა1,2480 kg/m
Colourwhite
MaterialPVC
Leadless materialyes
Self-extinguishing30 s
Temperature resistance-5 - 60 °C
Flaming loop test850 °C
Mechanical protectionIK07
Impact resistance1 J
Antibacterialyes
Width118 mm
Height54 mm
Length2 m
Inside area1550, 2250
Allowance
The trunkings are available in lengths with a tolerance of ± 0.5% at 20 ° C.
Use
they are resistant to aggressive and chemical environments. They do not resist UV radiation, they are not suitable for outdoor use.
Manufactures´s recommendations
The producer recommends checking the depth of a particular device before installation.
Area with explosion danger
Electro-installation trunking (insertive, rectangular, halogen-free) and parapet canals with accesories can be installed in zones with explosion hazard of flammable gases (zone 2) and with the risk of explosion of flammable dusts (zone 22), installation must comply with EN 60079-14.
Fire reaction class of underlying materialA1 - F
Protection typesIP 40
StandardsČSN EN 50 085-1
Package descriptionpackage - cardboard
With protective foilyes

Designed for installation of modular devices 45x45 or 45x22,5 mm. KOPOS recommends installing QUADRO instruments, tailor-made for KOPOS products. The installation devices from other manufacturers is possible e.g. ABB, PEHA, Legrand, OBO Bettermann, Schneider Electric Altira with maximal instrument depth 42 mm. The tilting section allows inserting the shielding canal SK 40X20 or SK 40X33, which ensures shielding of data circuits. If shielding and therefore inserting shielding canals is required, parapet trunking must be installed with tilting section up. Maximum number of modular instruments placed next to each other is 3 pcs. When installing multiple instruments next to each, it is necessary to put about 5 cm wide piece of lid after 3 pieces to fasten them.  There is no need to use any covers for the final installation of modular devices. The lid is cut to the desired length and inserted next to the instrument. Registered industrial design.