EAN code8595057631861
Customs code39172290
წონა0,0810 kg/m
Colourlight grey
MaterialPC-ABS
Halogen free materialyes
Self-extinguishing30 s
Temperature resistance-45 - 90 °C
Mechanical resistance320 N/5cm
Mechanical protectionIK06
Length3 m
Outside diameter20 mm
Inner diameter (min.)17,1 mm
Allowancelength ± 10 mm
Manufactures´s recommendations
The producer recommends the installation of plastic pipes at temperatures above 0 ° C.
Funcionality in fireP90-R, E90, PS90
Area with explosion danger
Can be installed in a zone with the danger of explosion of flammable gases and vapors of zone 2 and into the zone of danger of explosion of flammable dusts of zone 22.
Fire reaction class of underlying materialA1 - F
Sorting code22521
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Max. load for fire resistance10 kg

Halogen-free rigid necked pipe suitable for distribution systems in apartments and industrial environments. Up to a diameter of 25, the pipes are rigid socket pipes at one end. Diameters 32 - 63 are fitted with a coupling. Halogen-free pipes are used on premises where the safety of people and property is primary, e.g.: public buildings, hospitals, schools, theatres, airport halls, shopping centres, etc.

Note for system with maintained functionality in fire:
max. 1 piece of cable in the pipe
You find more information in the catalogue Systems with maintained functionality in fire.

ამჟამად არ არის პროდუქცია.