EAN code8595568927583
Customs code73269098
წონა0,0712 kg/pcs
Materialsteel
Surface finishElectrolytic Galvanized
Temperature resistance-45 - 250 °C
Width15 mm
Height73 mm
Length73 mm
Pipe outside diameter63 mm
Inner diameter63 mm
Funcionality in fireP90-R, E90, PS90
Thread typeM6
Sorting code3456210
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
For pipes63
Max. load for fire resistance
is determined by the weight of the inserted cables

For fixing to the base material are suitable the KPO 6 anchors or KPOZ 6 anchor in combination with ZT 6 threaded rod, SVD screws in wood, KHP + ZT 6 in aerated concrete. The recommended cable diameters correspond to the size of the clamp with a small reserve. To easier assembly the clamp is provided with a groove for insertion, during assembly it is not necessary the upper part of the clamp completely separate. Anchor KHP with SVD screw is used for anchoring to porous concrete. For more information check catalogue Systems with maintained functionality in fire.

Note for system with maintained functionality in fire:
To fix the connection use threaded rod ZT6 with knocking anchor or anchor KPO 6 .
You find more information in the catalogue Systems with maintained functionality in fire.