EAN code8595057628380
Customs code73089059
წონა0,2940 kg/pcs
Surface finishPre-Galvanized
Temperature resistance-50 - 150 °C
Funcionality in fireP90-R, E90, PS90
StandardsČSN EN 61537
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Thickness of metal sheet1 mm
Quantity of screws for connecting8
Dimension H65 mm
For height of cable tray60 mm

It is used for making an additional branching use an unequal T-piece or cross. Advantage of this using is availability to choose bending tray with any width. The reduction piece is delivered in singles, must be used 2 pieces for installation. The connection is performed using the bolts NSM 6X10. The cover of a horizontal VOH branch can be used to cover routes with a reduction piece.

Note for system with maintained functionality in fire:
You find more information in the catalogue Systems with maintained functionality in fire.